Inverter HP Mini Generasi ka-4 sareng Charger 600W/1000W/1500W
HP Mini Series Pure Sine Wave Inverter & Charger
♦ Ultra Low THD, Ilaharna 7% Dina Beban linier Pinuh
♦ MPPT Solar carjer controller Sadia
♦ Remote Control Sadia
♦ Batré Suhu Sensing Pikeun Ngaronjatkeun Ngecas Precision
♦ Otomatis Gen Mimitian Fungsi Pikeun Pareum Grid System Jeung Generator Salaku Daya Nyadangkeun
Fitur HP Series Inverter & MPPT & Charger
Fitur
♦ Smart Jauh Control
♦ Rojongan Panel Surya jeung Fungsi MPPT
♦ Dirancang pikeun Beroperasi dina Lingkungan Kasar
♦ Mimitian DC & Fungsi Diagnostik Diri Otomatis
♦ Cocog sareng Beban Linier & Non-Linear
♦ Gampang Pasang & Gampang Dioperasikeun & Gampang Direngsekeun
♦ Low DC Tegangan Ngarojong Perkakas Imah & Kantor
♦ Laju Ngecas Kuat Nepi ka 120Amp, Bisa Dipilih Tina 0% -100%
♦ Desain Efisiensi Tinggi & "Mode Hemat Daya" pikeun Ngahémat Énergi
♦ Modeu Prioritas Batré, nunjuk Konfigurasi UPS Inverter-Preferred
♦ 13 Vdc Batre titik cageur, Dedicated pikeun Sistem Énergi Renewable
♦ 8 Pre Set Batré Tipe Selector Ditambah De-sulphation pikeun accu sagemblengna datar
♦ 4-léngkah ngecas Batré Intelligent, PFC (Power Factor Correction) pikeun Charger
♦ 8 ms Waktos Transfer Biasa Antara Utiliti & Batré, Ngajamin Kontinuitas Daya
♦ 15s Tunda Sateuacan Mindahkeun nalika AC Resumes, Perlindungan pikeun Beban nalika Dipaké sareng Generator
HP MINI Pure Sinus Wave Inverter / carjer | |||
Spésifikasi listrik | |||
Inverter Kaluaran | Peunteun kakuatan | 600W | 1000W |
Daya Kaluaran kontinyu | 600W | 1000W | |
Peunteun Lonjakan (20s) | 1800W | 3000W | |
Bentuk gelombang kaluaran | Gelombang PureSine/Sarua jeung input (mode Bypass) | ||
Efisiensi nominal | 80% (puncak) | ||
Efisiensi Mode Line | <95% | ||
Faktor kakuatan | 0.9-1.0 | ||
Tegangan kaluaran nominal RMS | 120Vac atanapi 230Vac | ||
Regulasi tegangan kaluaran | ± 10% RMS | ||
Frékuénsi Kaluaran | 50/60Hz ± 0,3Hz | ||
Protection Circuit pondok | Sumuhun, Fungsi Wates Ayeuna (Full sanggeus 1sec) | ||
waktos mindahkeun has | 10 ms (Max) | ||
THD | Ilaharna <3%, Max 10% dina beban liner pinuh | ||
Input DC | Tegangan Input Nominal | 12.0Vdc | |
Tegangan Mimitian Minimum | 10.0Vdc | ||
Alarm Batré Lemah | 10.5Vdc / 11.0Vdc | ||
Perjalanan Batré Lemah | 10.0Vdc / 10.5Vdc | ||
Alarm Tegangan Tinggi & Sesar | 16.0Vdc | ||
High DC Input Pamulihan | 15.5Vdc | ||
Tegangan Batré Lemah Pulihkeun | 13.0Vdc | ||
Modeu Konsumsi-Paluruhan dianggurkeun | <25W nalika Power Saver on | ||
AC carjer | Input Range tegangan | Sempit: 100-135VAC / 194-243Vac | |
lebar: 90-135VAC / 164-243Vac | |||
Input rentang Frékuénsi | Sempit: 47-55±0.3Hz pikeun 50Hz,57-65±0.3Hz pikeun 60Hz | ||
lebar: 43±0.3Hz tambah pikeun 50Hz/60Hz | |||
Tegangan kaluaran | Gumantung kana jenis batré | ||
Peunteun Pemutus Charger (120Vac) | 7A | 10A | |
Laju Muatan Max | 20A ka 25A +/- 5A, gumantung kana modél | ||
Over Charge Protection Pareum | 15.7V pikeun 12Vdc | ||
Jenis Batré | Fsat Vdc | Ngambang Vdc | |
Gél AS | 14 | 13.7 | |
A, GM 1 | 14.1 | 13.4 | |
AGM 2 | 14.6 | 13.7 | |
Asam kalungguhan disegel | 14.4 | 13.6 | |
Gél Euro | 14.4 | 13.8 | |
Buka Asam Timah | 14.8 | 13.3 | |
Kalsium | 15.1 | 18.6 | |
De-sulphation | 15,5 pikeun 4 jam | ||
Kadali jauh | Sumuhun.Pilihan | ||
Bypass & Protection | Input Tegangan Gelombang | Gelombang Sinus (Grid atanapi Generator) | |
Tegangan nominal | 120Vac | 230Vac | |
Low Tegangan Trip | 80V/90V±4% | 184V/154V±4% | |
Low Tegangan ulang kalibet | 90V/100V±4% | 194V/164V±4% | |
High Voltege Trip | 140V±4% | 253V±4% | |
Tegangan tinggi ulang kalibet | 135V±4% | 243V±4% | |
Max Input Tegangan AC | 150VAC | 270VAC | |
Frékuénsi Input nominal | 50Hz atanapi 60Hz (Otomatis ngadeteksi) | ||
Low Freq Trip | Sempit: 47±0.3Hz pikeun 50Hz,57±0.3Hz pikeun 60Hz | ||
Lebar: 40±0.3Hz pikeun 50Hz/60Hz | |||
Low Freq ulang kalibet | Sempit: 48±0.3Hz pikeun 50Hz,58±0.3Hz pikeun 60Hz | ||
Lebar: 45±0.3Hz pikeun 50Hz/60Hz | |||
High Freq Trip | Sempit: 55±0.3Hz pikeun 50Hz,65±0.3Hz pikeun 60Hz | ||
lebar: Taya up wates pikeun 50Hz/60Hz | |||
High Freq ulang kalibet | Sempit: 54±0.3Hz pikeun 50Hz,64±0.3Hz pikeun 60Hz | ||
lebar: Taya up wates pikeun 50Hz/60Hz | |||
Spésifikasi mékanis | Ukuran Inverter (L * W * H) | 325*173*135mm/12.8*6.8*5.3 〞 | 362*173*135mm/14.3*6.8*5.3 〞 |
Beurat Inverter | 7.5KG/16.5Ib | 11KG/24.3Ib | |
Ukuran Pengiriman (L * W * H) | 425*230*205mm/16.7*9*8〞 | 475*230*205mm/18.7*9*8〞 | |
Beurat pengiriman barang | 8.5KG/18.7Ib | 12KG/26.5Ib | |
tampilan | Status LED | ||
Garansi Standar | 1 Taun |
Dina panel pungkur inverter, aya 5 saklar DIP anu ngamungkinkeun para pangguna pikeun ngaluyukeun kinerja alat.
Pindah NO | Pindah Fungsi | Posisi: 0 | Posisi: 1 | |
SW1 | Low Batré Trip Volt | 10.0VDCPikeun Batré Deep-Cycle | 10.5VDCPikeun Mimitian Batré | |
* 2 pikeun 24Vdc, * pikeun 48Vdc | ||||
SW2 | Rentang Input AC | Sumber AC | Pikeun Utiliti Mode | Pikeun Generator Mode |
230Vac HV | 184-253Vac | 140-270Vac | ||
120Vac LV | 100-135Vac | 90-135Vac | ||
SW3 | Power Saver Otomatis Setélan | Peuting Charger Fungsi | Ngadeteksi Beban Per 3Secs | |
SW4 | Setélan Frékuénsi O/P | 50Hz | 60Hz | |
SW5 | Solar / AC Prioritas Setélan | Prioritas Utiliti | Prioritas batré |
Volt Perjalanan Batré Lemah:
Volt Trip Batré Lemah disetel dina 10.0VDC sacara standar.Éta tiasa disaluyukeun kana 10.5VDC
Rentang Input AC:
Aya rentang input AC anu béda-béda pikeun rupa-rupa beban.Éta tiasa disaluyukeun tina 184-253VAC ka 140-270VAC.
Siklus sensing beban:
Inverter ieu pabrik defaulted pikeun ngadeteksi beban pikeun 250ms dina unggal 30 detik.Siklus ieu tiasa disaluyukeun kana 3 detik ngalangkungan SW3 dina saklar DIP.
Frékuénsi nyaluyukeun:
Frékuénsi inverter diatur ku Sw4.Konfigurasi standar pabrik pikeun 220/230/240VAC inverter nyaeta 50Hz, sarta 60Hz pikeun 100/110/120VACinverter.Sedengkeun freq kaluaran bisa gampang dirobah sakali freq mumpuni dilarapkeun ka inverter nu.
Setélan Prioritas Solar / AC:
Inverter kami dirancang prioritas AC sacara standar.Ieu hartosna, nalika input AC aya, batréna bakal dicas heula, sareng inverter bakal mindahkeun input AC pikeun ngawasa beban.Saklar Prioritas AC sareng Prioritas Batré sayogi upami dipénta.Lamun anjeun milih prioritas batré, inverter bakal inverting tina batré sanajan input AC.